CE-150

Manufactured by: CE-150

// AC/DC Power Supplies / Open Frame | Enclosed | U-Chassis

Download PDF Specs »

Features:

  • RoHS Compliant
  • Universal 85~264 VAC input
  • Compact Size
  • One to four tightly regulated outputs
  • EN 60950-1 ITE Certification
  • EN 60601-1 Medical Certification
  • Class B Emissions per EN 55011/22
  • Harmonic Current per EN 61000-3-2
  • EMC to EN 61000-6-2 & EN 60601-1-2
  • Optional perforated cover

General Specifications

  • Manufacturer Integrated Power Designs
  • Form Factor U Bracket
  • Power 150 Watts
  • Input 85-264 VAC
  • Outputs Sinlge, Dual, Triple, or Quadruple
  • Warranty 2 Year Warranty

Models

Model #

Output

  • CE-150-4001 3.3V, 5V, 12V, -12V
  • CE-150-4002 5V, 3.3V, 12V, -12V
  • CE-150-4003 5V, 3.3V, 15V, -15V
  • CE-150-4004 5V, -5.2V, 12V, -12V
  • CE-150-4005 5V, -5.2V, 15V, -15V
  • CE-150-4006 5V, 12V, 12V, -12V
  • CE-150-4007 5V, 12V, 15V, -15V
  • CE-150-4008 15V, -15V, 24V, 24V
  • CE-150-4009 5V, 12V, 15V, -12V
  • CE-150-4011 5V, 12V, -5V, -12V
  • CE-150-4101 5V, 24V, 12V, -12V
  • CE-150-4102 5V, 24V, 15V, -15V
  • CE-150-4103IT 5V, 24V, 12V, -12V
  • CE-150-3001 5V, 12V, -12V
  • CE-150-3002 5V, 15V,-15V
  • CE-150-3003 15V, -15V, 5V
  • CE-150-3004 5V, 15V, 36V
  • CE-150-2001 12V, -12V
  • CE-150-2002 15V, -15V
  • CE-150-2003 5V, 12V
  • CE-150-2101 5V, 24V
  • CE-150-1001 3.3V
  • CE-150-1002 5V
  • CE-150-1003 12V
  • CE-150-1004 15V
  • CE-150-1005 24V
  • CE-150-1006 28V
  • CE-150-1007 48V

Mechanical

  • Dimensions 4.0 x 7.0 x 1.75 inches
  • Operating Temperature 0°C + 70°C
  • MTBF 150,000 Hours min, MIL-HDBK-217F, 25°C, GB
  • Cooling Method Free air convection, LFM Forced Air
  • Agency Approvals General: Protection Class- I, Over voltage catagory- II, Pollution Degree- 2
    UL: UL 60950-1, UL 60601-1, CAN/CSA-C22.2 No. 60950-1-03, CAN/CSA-C22.2 No.601-1-M90
    with updates 1 and 2
    TUV: EN 60950-1:2001, EN 60601-1/A2:1995
    CE: Low Voltage Dir

Output

  • Voltage Accuracy Output 1: ±0.25%
    Output 2: ±0.25%(X0XX) ±3%(X1XX)
    Output 3: ±2%
    Output 4: ±2%
  • Line Regulation 0.50%
  • Load Regulation Output 1: 0.5%
    Output 2: 0.5%(X0XX) 3%(X1XX)
    Output 3: 2%
    Output 4: 2%
  • Minimum Load 10%
  • Protections Output Over Voltage Protection: Output 1- 110%-150%, shuts down all outputs. Cycle input to restart
    Output Over power protection: 165 W min, Outputs 1 and 2; Outputs cycle on/off, auto recovery
    Output Over Current Protection: 110% min, Outputs 3 and